216357,t ORDINANCES
a .•i'/ri8inal to City Clerk � 11
4 Qouncil File No. 218357- 0rdinance No.
12664 —By Frank L. Loss— �
ORDIN m Ordinance mending Chapters If i.►d
6 20 ,+ a the Saint Paul Legi•�
°atsa ?a- :t ^in9ng to `4 � NO.
'3 ap gc
Frank Loss ��alr 3 ' -"' ` }-e F
PRESENTED BY • ` 6RDINANCE NO
1
_JrN�
JU
:0
nc
IL
C„
) Z
II11je
V
An ordinance amending Chapters 16, 18, 19 and 20 of the
Saint Paul Legislative Code pertaining to Building Construc-
tion. This is an emergency ordinance rendered necessary for
the preservation of public peace, health and safety.
THE COUNCIL OF THE CITY OF SAINT PAUL DOES ORDAIN:
Section 1 - That Section 16.04 Technical Regulations for
,Gas Burner Installations of Input Capacity 400,000 BTU per
Hour and Smaller is hereby amended by deleting subsection 7
Ventilation, which reads as follows:
7. Ventilation.
Gas burners and gas burning appliances as hereinbefore
defined shall not be installed for operation in a room
where the normal, facilities for ventilation do not permit,
proper combustion of the gas, unless special provision is
made for supplying sufficient air for complete combustion.
and add the following in lieu thereof:
7.. Ventilation
Gas burners and gas burning equipment as hereinbefore
defined shall not be installed for operation in a room
where the normal facilities for ventilation do not permit
proper combustion of gas, unless special provision is made
for supplying sufficient air for complete combustion as '
provided in Section 16.07 Provisions For Combustion Air and
Equipment Room - Ventilation For Gas Fired Equipment.
- Section 2 - That Section 16.04 Technical Regulations For
Gas Burner Installations of Input Capacity of 400,000 BTU Per
Hour And Smaller is hereby amended by deleting subsection
11 Flue Pipes, which reads as follows:
11. Flue Pipes,
a. The internal cross - sectional area of the flue pipe
between the appliance and the chimney liner shall be such
as to provide not less than one (1) square inch of flue
area per 7,500 hourly BTU input. In no case shall this
flue Pipe be less than five (5) inches'in diameter for cen-
tral heating gas appliances nor less than four (4) inches
in diameter for space heating appliances and it shall not
be larger than the`next integral inch diameter above the
size given in the following Table No. 1.
32/
ql�,
Yeas Councilmen Nays Passed by the Council
Dalglish
Holland
Loss Tn Favor
Mortinsan
Peterson Against
Rosen
Mr. President (Vavoulis)
Approved:
Attest: t
City Clerk .Xayor
1M 6-62 -060-22/, 4
a ` 'Vrl$inal to- City Clerk
r
V�
t
ORDINANCE
COUNCIL FILE NO
PRESENTED BY ORDINANCE NO. /"� to �
ation of Residence `hype Warm Air Heating and Air Condition-
ing Systems are hereby adopted by reference as requirements
for Warm Air Heating-And Ventilation work in the City of
Saint Paul with additions and exceptions as provided herein.
Section. 11 - This ordinance is hereby declared to be an
emergency ordinance rendered necessary for the preservation of
public peace, health, and safety. _
Section 12 - This ordinance shall take effect and be in
force from and after its passage and publication.
Yeas Councilmen Nays
Dalglish
Holland
Loss
Mortinson
Peterson
Rosen
Mr. President' (V is)
Attest : •
,.. City Clerk
1111 6-62 22
10
FEB 131964
Passed by the Council
Tn Favor
6 Against
1 FEB 131964
IL
Mayor
14 t:� +fir r.+k J,. -i _._.. �.?�"� ^-• `�
Duplicate tp Printer
ORDINANCE
PRESENTED BY Frank L. Loss
COUNCIL FILE NO.
(� Ivy,a 51
ORDINANCE NO.
6�-
An ordinance amending Chapters 16, 18, 19 and 20 of the
Saint Paul Legislative Code pertaining to Buildincf Construc-
tion. This is an emergency ordinance rendered necessary for
the preservation of public peace, health and safety.
THE COWCIL OF THE CITY OF SAINT PAUL DOES ORAAINs
Section 1 - That Section 16.04 Technical Regulations for
Gas Burner Installations of Input Capacity 400,000 BTU per
Hour and Smaller is hereby amended by deleting subsection 7
Ventilation, which reads as follows:
7. Ventilation
G burners and gas burning appliances as hereinbefore
defi d shall not be installed for operation in a room
where, the normal facilities for ventilation do not permit
propat combustion of the gas, unless special provision is
madeifor supplying sufficient air for complete combustion.
and adck. the following in lieu thereof:
7 Ventilation
G burners and gas burning equipment as hereinbefore
defi�d shall not be installed for operation in a room
where'!the normal facilities for ventilation do not permit
proper combustion of gas, unless special provision is made
for supplying sufficient air for complete combustion as
provided in Section 16.07 Provisions For Combustion Air and
Equipment Room,Ventilation For Gas Fired Equipment.
Section 2 That Section 16.04 Technical Regulations For
Gas Burner Installations of Input Capacity of 4000000 BTU Per
Hour And Smaller is hereby amended by deleting subsection
11 Flue Pipes, which reads as follows:
11. Flue Pipes
a. The internal cross - sectional area of the flue pipe
between the appliance and the chimney liner shall be such
as to provide not less than one (1) square inch of flue
area per 7,500 hourly BTU input. In no case shall this
flue Pipe be less than five (5) inches in diameter for cen-
tral heating gas appliances nor less than four (4) inches
in diameter for space heating appliances and it shall not
be larger than the next integral inch diameter above the.
size given in the following Table No. 1.
Yeas Councilmen Nays
Dalghsh
Holland
Loss
Mortinson `
Peterson
Rosen
Mr. President (Vavoulis)
Attest:
City Clerk
1M 6-62 22
Passed by the Council
Approved:
Mayor
Tn. Favor
Against
nnpllexta to Printer
PRESENTED BY
ORDINANCE
COUNCIL FILE NO.
ORDINANCE NO.
ation.of Residence Type Warm Air Heating and Air Condition -
ing Systems are hereby adopted by reference as requirements
for Warm Air Heating And Ventilation work in the City of
Saint Paul with additions and exceptions as provided herein.
Section 11 - This ordinance is hereby declared to be an
emergency ordinance rendered necessary for the preservation of
public peace, health, and safety.
Section 12 -'this ordinance shall take effect and be in
force from and after its passage and publication.
Yeas Councilmen Nays
Dalglish
Holland
Loss
Mortinson
Peterson
Rosen
Mr. President (Vavoulis)
Attest:
City Clerk
1D1 8-82 X22
V
10
Passed by the Council �+
7 In Favor
Aroainst
I Z 7v�
Approved:
Mayor
TABLE N0. 1
MINIMUM PERMISSIBLE FLUE SIZES FOR
GAS BURNER INSTALLATIONS
NOTES: (1) This table is based on one (1) sq. in. of flue
area per 7,500 BTU per hour input.
(2) If flue pipe exceeds ten (10) feet in length or
contains more than two elbows, use next size
pipe and draft hood.
(3) In cases where the outlet from the appliance is
larger than the above indicated size, an orifice
plate may be inserted, or a section of the flue
pipe restricted' to the size indicated.
(4) In special cases with high chimneys or flues, the
above schedule or areas may be modified subject
to specific approval by the Bureau.
r
b. The draft hood should ordinarily be located adjacent
to the appliance. In cases where it appears desirable to
place the draft hood at a distance from the appliance, the
size of the restricted section may be modified according to
the length and rise of the flue pipe.
c. The proportioned section of the flue outlet of the
appliance eliminates the necessity of using an adjustable
damper in the flue pipe and -such damper will not be permit-
ted.
d, Where dampers are an integral part of the boiler or
furnace, they shall be removed or permanently secured in
the_ wide open position, except such dampers, the function
of which is to alter the passage of flue gases through the
appliances, which shall be locked in such a position as not
to interfere with the normal operation of the burners.
e. Material used for flue pipe shall be such as to re-
sist the corrosive action of flue gases.
f. Flue pipe of existing systems shall be relocated
where necessary and new flue pipe.installations shall be made
as to avoid sharp turns or other constructional features
which would create excessive resistance to the flow of the
-2-
Area Of
Diameter of
Input Rating
Flue Outlet
Flue Pipe
(BTU per Hour)
(Sq. In.)
(Inches)
94,500
12.6
4
147,000
19.6
5 J
f 212,250
28.3
6
288,750
38.5
7
377,250
50.3
8
477,000
63.6
9
NOTES: (1) This table is based on one (1) sq. in. of flue
area per 7,500 BTU per hour input.
(2) If flue pipe exceeds ten (10) feet in length or
contains more than two elbows, use next size
pipe and draft hood.
(3) In cases where the outlet from the appliance is
larger than the above indicated size, an orifice
plate may be inserted, or a section of the flue
pipe restricted' to the size indicated.
(4) In special cases with high chimneys or flues, the
above schedule or areas may be modified subject
to specific approval by the Bureau.
r
b. The draft hood should ordinarily be located adjacent
to the appliance. In cases where it appears desirable to
place the draft hood at a distance from the appliance, the
size of the restricted section may be modified according to
the length and rise of the flue pipe.
c. The proportioned section of the flue outlet of the
appliance eliminates the necessity of using an adjustable
damper in the flue pipe and -such damper will not be permit-
ted.
d, Where dampers are an integral part of the boiler or
furnace, they shall be removed or permanently secured in
the_ wide open position, except such dampers, the function
of which is to alter the passage of flue gases through the
appliances, which shall be locked in such a position as not
to interfere with the normal operation of the burners.
e. Material used for flue pipe shall be such as to re-
sist the corrosive action of flue gases.
f. Flue pipe of existing systems shall be relocated
where necessary and new flue pipe.installations shall be made
as to avoid sharp turns or other constructional features
which would create excessive resistance to the flow of the
-2-
-flue gases. Flue pipes shall slope upward to chimney. / �o
g.. Flue pipe shall be tightly connected to the chimney
liner,. so as to prevent infiltration of cold air.
h. No baffles shall be applied which will interfere
with the proper combustion of the gas.
i. Flue pipe shall be well supported to prevent sag-
ging and shall not be installed closer than six (6) inches
to any combustible building materials unless flue pipe
is covered with incombustible insulation such that the
surface temperature of the exterior surface thereof attain
a temperature not higher than one hundred twenty -five (125)
degrees Fahrenheit when the appliance is under continuous
operation.
j.. All space heating equipment shall be of the vented
type and properly vented to an effective flue. Space heat-
ers shall have one hundred (100) per cent shut -off.
k. Radiant heaters or other unvented heaters of less
than 25,000 BTU input may be installed in fireplaces provid-
ing the chimney has a positive draft with the damper closed.
and add the following in lieu thereof:
11. Flue Pipes (Breeching)
a. For equipment or appliances specifically designed
to burn only gas, the internal cross - sectional area of the
flue pipe between the equipment or appliance and the chim-
ney liner shall be such as to provide not less than one (1)
square inch of internal cross - sectional area per 7500 hour-
ly BTU input in accordance with Table I herein. In no case
shall this flue pipe be less than five (5) inches in diam-
eter or equivalent cross - sectional area for central heating
equipment or four (4) inches in diameter or equivalent
cross - sectional area for space heating equipment and
further, in no case shall this flue pipe have an internal
cross - sectional area less than the internal cross - sectional
area of the flue collar opening as provided on the equip-
ment or appliance by the manufacturer, regardless of input
rating.
b. For installation of gas conversion burners in equip
ment or appliances originally designed for burning various
fbels including but not specifically gas, the internal
cross - sectional area of the flue pipe between the equipment
or appliance and the chimney liner shall be such as to
provide not less than one (1) square inch of flue area per
7500 hourly BTU input. In no case shall this flue pipe
be less than five (5) inches in diameter or equivalent
cross - sectional area for central heating equipment or less
than four (4) inches in diameter or equivalent cross -
sectional area for space heating equipment and it shall
not be larger than the next integral inch diameter above
the size given in the following Table No. 1.
-3-
TABLE NO. 1
Minimum Permissible Flue Sizes For
Gas Burner Installations
Input Rating Area of Diameter of
P 9 Flue Outlet Flue Pipe
(BTU per Hour) (Sq. Inches) (Inches)
94,500 12.6 4
147,000 19.6 5
212,250 28.3 6
288,750 38.5 7
377,250 50.3 8
477,000 63.6 9
Notes: (1) This table is based on one (1) sq. in. of flue
area per 7500 BTU per hour input.
(2) If flue pipe exceeds ten (10) feet in length or
contains more than two elbows, use next size
pipe and draft hood.
(3) In special cases with high chimneys or flues,
the above schedule or areas may be modified sub-
ject to specific approval by the Bureau.
(4) In cases where the outlet from the equipment to
be converted is larger than the above indicated
size, an orifice plate may be inserted, or a
section of the flue pipe restricted to the size
indicated. The plate or restriction must be
installed between the equipment and the draft
hood.
(5) The draft hood should ordinarily be located ad-
jacent to the equipment. In cases where it ap-
pears desirable to place the draft hood at a
distance from the equipment, the size of the
restricted section may be modified according to
the length and rise of the flue pipe.
(6) The proportioned section of the flue outlet of
the equipment eliminates the necessity of using
an adjustable damper in the flue pipe and such
damper will not be permitted.
(7) Where dampers are an integral part of the equip-
ment to be converted, they shall be removed or
permanently secured in the wide open position,
except such dampers, the function of which is to
alter the passage of flue gases through appli-
ances, which shall be locked in such a position
as not to interfere with the normal operation of
the burners..
MC
c. Material used for flue pipe shall be such as to re-
sist the corrosive action of flue gases.
d. Flue pipe of existing systems shall be relocated
where necessary and new flue pipe installations shall be
made as to avoid sharp turns or other constructional
features which would create excessive resistance to the
flow of flue gases.
e. Changes in cross - sectional areas in flue pipe and
Venting systems shall be accomplished by properly design-
ed and tapered transformations or other similar appropriate
fittings and shall be subject to approval by the Bureau.
f. Flue pipe shall slope upward to the chimney at a
grade of not less than one quarter (14) inch per foot of length
unless otherwise approved by the Bureau.
g. Flue pipe shall be tightly connected to the chimney
liner so as to prevent infiltration of cold air.
h. No baffles shall be applied which will interfere
with the proper combustion of the gas and /or proper vent-
ing of the equipment.
i. Flue pipe shall be well supported to prevent sagging
and shall not be installed closer than six (6) inches to
any combustible building materials unless flue pipe is cov-
ered with noncombustible insulation such that the surface
temperature of the exterior surface thereof will not exceed
one hundred twenty -five (125) degrees Fahrenheit when the
appliance is under full, continuous operation.
j. All space heating equipment shall be of the vented
type and properly vented to an effective flue. Space heaters
shall have one hundred (100) per cent shut -off.
k. Radiant heaters or other unvented heaters not exceed-
- ing 25,000 BTU per hour input may be installed in fireplaces
providing the chimney has a positive draft with the damper
closed.
Section 3 - that Section 16.05 Technical Regulations For
Gas Burner Installations, Exceeding 400,000 BTU Per Hour Input
is hereby amended by adding the following to subsection 15
Air Intakes.
The area of fresh air intakes for combustion air and
equipment room ventilation shall be in accordance with
Section 16.07 Provisions For Combustion Air And Equipment
Room Ventilation For Gas Fired Equipment.
-5-
�l 1
Section 4 - that Chapter 16 Gas Space Heating Requirements
is hereby amended by adding Section 16.07 Provisions For Com-
bustion Air find Equipment Room Ventilators For Gas Fired Equip-
ment, which reads as follows:
16.07 Provisions For Combustion Air And Equipment Room
Ventilators For Gas Fired Equipment
1. For heating equipment installed with a draft hood, the
air requirement for primary and secondary air,excess air, and
dilution air is 30 cubic feet for each cubic foot of gas input.
The following table for certain selected inputs is based on a
reasonable velocity (300 FPM) and a reasonable pressure drop
across the grilled intake (0.030.05" H20)
Overall
Input Air Reqd. Size of Intake (50% Free Area)
75,000 BTUH
37.5 CFM
0.25
sq. ft.or 36 sq. in.
100,000
50
0,333
48
150,000
75
0.50
72 '
200,000
100
0.667
96
250,000
125
0.833
120
300,000
150
1.00
144
400,000
200
1.333
192
500,000
250
1.667
240
600,000
300
2.00
288
700,000
350
2.33
336
800,000
400
2.667
384
900,000
450
3.00
432
1,000,000
500
3.33
480
2. For heating equipment.installed with a barometric damp-
er, the excess air and dilution air requirements are reduced
and total air requirement becomes 17.5 cubic feet for each
cubic foot of gas input. The following table is based on the
same velocity and pressure drop as in Section 1.
Input
Air Read.
400,000 BTUH
120 CFM
450,000
135
500,000
145
600,000
175
700,000
205
800,000
235
900,000
265
1,000,000
295
1,250,000
365
1,500,000
435
1,750,000
505
2,000,000
575
Overall
Size of Intake (50% Free Area
0.8 sq. ft.
115 sq. in.
0.9
130
0.97
140
1.17
168
1.37
197
1.57
226
1.77
255
1.97
284
2.43
350
2.90
417
3.37
485
3.83
552
I� Y
3. For heating equipment
other similar types of draft
requirement is 15 cubic feet
gas input The foll t
installed with uptake dampers or
control equipment, the total air
of air for each cubic foot of
bI
owing a e is based on the same velocity
and pressure drop as in Sections 1 and 2.
Overall
Input Air Read. Size of Intake (50% Free Area)
750,000 BTUH
187.5 CFM
1.25 sq. ft.
180 sq. in.
800,000
200.0
1.33
192
900,000
225.0
1.50
216
1,000,000
250.0
1.67
240
1,500,000
375.0
2.50
360
29000,000
500.0
3.33
480
2,500,000
625.0
4.17
600
3,000,000
750.0
5.00
720
It should be noted that the sizes indicated are for gravity
intakes communicating directly to the outdoors and, while al-
lowance has been made for ordinary equipment such as bird
screens, etc.., no allowance has been made for-duct losses. Siz-
es shall be increased accordingly for any appreciable amount
of duct work and /or other restrictions placed in the intake.
For systems equipped with an intake fan, the air requirements
indicated shall be used in determining fan capacities.
For intetior, or alcove install ttons pf eguipmen�; -of the
normal esid.ential size
'r..,_ s wi:th� .vin'_. ;3;lati:otz� ;�3.r�.ftom An tide'
bui�.ding;� 'then..xe irement > s the
qu $ Of -Nat ona_i Boud A- ",t: ;te Under- '
�5`�errlters cim hl:et 54 da a `A" .r` 9, .:sYi�1�. a ` 1
. ,- d':_ ugu t' M 1.. PP Y3 two
.�' openi�nga;-_ one at to 6f ,exiclosure arid_ aiie at bottom; dae `
,%* th- _a Ttee ;area of --(1 s ar. s. gi
r: �:. qu e . inch., Per ,1000 BTUH ingUt;
.thesa� openings shall com* date; .with lhte ior, . areas having
adequate inflltxat gn4;fro ;.the Ou.t � ^Other ventilation:
rmeth,od "sacceptal�ie under :ecuiremnts. of t�F(J� „54 shall he con-
M .s der'ecl - acceptable- by- tli` Bureau where'' the above conditions
do not apply.
For Incinerators 1.5 CFM for each pound per hour capacity
shall be provided. -
Section 5 - that Section 18.17 Appliance Installation is
hereby amended by adding the following to item e:
The minimum area for fresh air intakes for combustion air
and equipment room ventilation shall be in accordance with
Section 16.07 Provisions For Combustion Air And Equipment
Room Ventilation For Gas Fired Equipment.
Section 6 - that Section 19.03 Permit Regulations is hereby
amended by deleting item a of subsection 1 Work For Which Permits
Are Required, which reads as follows:
a. It shall hereafter be unlawful for any person, firm or
corporation to construct or install any heating plant or
equipment, such as is subject to regulation by the provisions
of this code, in or for any building or to alter or repair
50
_DLOO
any such existing heating plant or equipment, without first
making written application to and securing a permit from the
Bureau therefor, or to fail or neglect to comply with the
provisions of this code and of the permit so issued thereunder,
and any person, firm or corporation, when applying for any such
permit shall, upon demand of said Bureau, furnish all necessary
plans, in duplicate, for such proposed construction, installa-
tion, alteration or repair and with all proper and sufficient
information relating thereto and shall secure the approval of
said plans before such permit shall be issued. All such plans
and /or specifications, except for single family or two family
dwellings or for heating installations wherein the space to be
heated does not exceed 100,000 cubic feet, shall be prepared
and signed by a "Registered Professional Engineer" duly qualified
by registration as required by "An Act to Regulate the Practice
of Architecture, Professional Engineering and Land Surveying,"
Chapter 523, Laws of 1921, as amended by Chapter 404, Laws of
1933, State of Minnesota, and by no other person or persons.
and substitute the following in lieu thereof:
a. It shall be unlawful for any person, firm or corporation
to construct or install any heating plant or equipment in any
building or to alter or repair any existing heating plant or
equipment without first making written application to and secur-
ing a permit from the Bureau therefor, or to fail or neglect to
comply with the provisions of this code and of any permit is-
sued thereunder. Plans shall be required in duplicate as provid-
ed in Section 1.08 Permits (Application, Issuance and Regula-
tions). Plans shall include in addition to the details of the
system to be installed, the heat loss for each room or area in-
cluded in the space to be heated.
Section 7 - that Section 19.05 Regulations is hereby amended
by deleting paragraph c of subsection 9, which reads as follows:
c. On single boiler installations of low pressure steam
systems, the return connections shall preferably be made
through a water line loop connection without check valves
(Hartford connections). Whenever a gate valve is provided
on the steam outlet from any boiler, a gate valve shall be
placed in the corresponding return to the boiler.
and insert the following in lieu thereof:
c. On low pressure steam systems involving single or multi-
ple boilers with gravity condensate return (including boiler re-
turn trap installations) the return connections shall be made
through a Hartford connection and safety loop on each boiler.
The safety loop shall be of proper size as approved by the Bur-
eau but not less than 2 -inch NPS, shall connect the steam out-
let or header to the return, and shall not be separated from
the boiler by any type of valve.
Section 8 - that Section 19.05, Regulations, is hereby
amended by deleting paragraph e of Subsection 9, which reads
as follows:
e. Each low pressure steam boiler installation shall have
an equalizing pipe of proper size, not less then two (2) inch,
connecting the steam outlet or header, to the return.
and insert the following in lieu thereof:
e.. Whenever a valve is provided on the steam outlet or
header of any boiler, a gate valve shall be placed in the
corresponding return to the boiler. Whenever a low pressure
steam system incorporates a boiler feed, pumped return, or
combination feed - return device, at least one check valve and
one gate valve shall be installed, respectively, between the
device and the boiler with the gate valve being located as
close to the boiler as possible,.
Section 9 - that Sectionr20.03 Warm Air Heating, Ventila-
tion And Sheet Metal Work Permit Regulations is hereby amended
by deleting item b of Subsection 2 Permit Application, Issu-
ance and Fees, which reads as follows:
b. No plan shall be approved or permit issued where the
building to be heated or ventilated exceeds 100,000 cubic
feet unless the plan so submitted shall be prepared and
signed by a registered professional engineer,duly qualified
by registration as required by an act to regulate the prac-
tice of architecture, professional engineering and land
surveying, Chapter 523, Laws of Minnesota for 1921, as amend-
ed by Chapter 404, Laws of Minnesota for 1933, and Chapter
380, Laws of Minnesota for 1945. Provided, however, that
the Bureau may waive the above requirement of a permit in the
case of alterations or repairs to any existing warm air heat-
ing or ventilation systems where the cost of such altera-
tions or repairs will not add to the required capacity of
such heating or ventilating systems, and are not, in the opin-
ion of said Inspector, of such a nature as to render an in-
spection of the same necessary or desirable.
and insert the following in lieu thereof:
b. Plans shall be submitted in duplicate as provided in
Section 1.08 Permits (Application, Issuance and Regulations).
Section 10 - that Section 20.03 Warm Air Heating, Venti-
lation And Sheet Metal Work, Permit Regulations is hereby furth-
er amended by adding item c to subsection 3 Publications as
folio*.
c. The National Fire Protection Association Pamphlet 90A
(1963 Edition) Standards For The Installation of Air Condi-
tioning and Ventilation Systems of Other Than Residence Type
and Pamphlet 90B (1961 Edition) Standards For The Installa-
• I
CITY OF SAINT PAUL]
ICanifal of Minnpcnfa i
Gs
BUREAU OF PUBLIC BUILDINGS ALFRED H. SCHROEDER, City Architect 445 City Hall, Zone 2 CApital 4 -4612 Ext. 361
January 16, 1964
RECEIVED
Hon.
Donald L. Lais JAN 17 1964
Corporation Counselor =;
CORPORATION_ C_QUNSEL
Dear Sir:
I am referring to you for your study and approval as to
form the enclosed copies of an ordinance which will amend
the Saint Paul Legislative Code, Chapters 16, 18, 19 and
20 referring generally to gas fired installations, boiler
installations, and permit regulations.
If this amendment meets with your approval as to form, I
would like to introduce it at an early council meeting.
Yours truly,
ank L. Loss
Commissioner
a
1 +a•r "
216"
TABLE NO. 1
MINIMUM PERMISSIBLE FLUE SIZES FOR / lc
GAS BURNER INSTALLATIONS
Area Of Diameter of
Input Rating Flue Outlet Flue Pipe
(BTU per Hour) (Sq. In.) (Inches)
94,500 12.6 4
147,000 19.6 5
212_,250 28.3 6
288,750 38.5 7
377,250 50.3 8
4770-000 63.6 9.
NOTES: (1) This table is based on one (1) sq, in. of flue
area per 7,500`BTU per hour input.
(2) If flue pipe exceeds ten (10) feet in length or
contains more than two elbows, use next size
pipe and draft hood.
(3) In cases where the outlet from the appliance is
larger than the above indicated size, an orifice
plate may be insertgd, or a section of the flue
pipe restricted to the size indicated.
(4) In special cases with high chimneys or flues, the
above schedule or areas may be modified_ subject
� to specific approval by the Bureay.
b. The draft hood should ordinarily be located adjacent
to,the appliance. In cases where it appears desirable to
place the draft hood at a distance from the appliance, the
size of the restricted section may be modified according to
the length and rise of the flue pipe:
c. The proportioned section of the flue outlet of the
appliance eliminates the necessity of using an adjustable
damper in the flue pipe and such damper will not be permit-
ted.
d, Where dampers are an integral part of the boiler or
tprnace, they shall be removed or permanently secured in
t-he wide open position, except" such dampers, the function
of which is to alter-the passage of flue gases through the
appliances, which shall be locked in such a position as not
to interfere with the normal operation of the burners.
e. Material used for flue pipe shall be such as to re-
sist-the corrosive action of flue gases. .
f. Flue pipe of existing systems shall be relocated
where necessary and new flue pipe installations shall be made
as to avoid sharp turns or other constructional features"
which would create excessive resistance to the flow of the
t -2-
..
211666
flue gases. Flue pipes shall slope upward to chimney. %
g.. Flue pipe shall be tightly connected to the chimney
.,liner, so as to prevent infiltration of cold air,
h. No baffles shall be applied which will interfere
with the proper combustion of the gas.
i. Flue pipe shall be well supported to prevent sag -
ging'and shall not be installed closer than six (6) inches
to any combustible building materials unless flue pipe
is covered with incombustible insulation such that the
surface temperature of the exterior surface thereof attain
a temperature-not higher than _one hundred twenty -five (125)
degrees Fahrenheit when the appliance is under continuous
operation, --
j.. All space heating equipment shall.be of the vented
type and properly vented to an effective flue. Space heat-
ers shall have one hundred (100) per cent shut -off.
k. Radiant heaters or other, unvented heaters of less
than 25,000 BTU input may be installed in fireplaces provid-
ing the chimney has a positive draft with the damper closed.--
and add the following in lieu thereof:
11. Flue Pipes (Breeching) ~�
a: For equipment or appliances specifically designed
to burn only gas, the internal cross - sectional area of the
flue pipe between the equipment or appliance and the chim-
ney liner shall be such as to provide nbt less than one (1)
square inch of internal cross - sectional area per 7500 hour-
ly BTU input in accordance with Table I herein. In -no case
shall this'flue pipe be less than five (5) inches in diam-
eter or equivalent cross - sectional area for central heating
equipment or four (4) inches in diameter or equivalent
cross - sectional area for space heating equipment and
further, in no case shall this flue pipe have an internal
cross- sectional area less than the internal cross - sectional
area of the flue collar opening as provided on the equip-
ment or appliance by_the manufacturer, regardless of input
rating.,
b. For installation of gas conversion burners in equip-
ment or appliances originally designed for burning various
fuels including but not specifically gas, the internal
cross - sectional area of the flue pipe between the equipment
or appliance and the chimney liner shall be such as to
provide not less than one (l) square inch of flue area.per
7500 hourly BTU input. In no case shall this flue.pipe
be less than five (6) inches in diameter or equivalent
cross - sectional area for central heating equipment or less
than four (4) inches in diameter or equivalent cross -
sectional area for space heating equipment and it shall
not be-larger than the next integral inch diameter above
the size given in* the following'Table No. 1..
-3-
Minimum
Gas
Input Rating
(BTU per Hour)
TABLE NO. 1
Permissible Flue Sizes.For
Burner Installations
Area of
Flue Outlet
(Sq. Inches)
42V 31:yj
1"n-6611
Diameter of
Flue Pipe
(Inches)
94,500 12.6 4
147,000 19.6 5
212,250 28.3 6
288,750 38.5 7
377,250 50.3 8
477;000 63.6 9
Notes: (1) This table is based on one (1) sq. in. of flue
area per 7500 BTU per hour input.
(2) If flue pipe exceeds ten (10) feet in length or
contains more than two elbows, use next size
pipe and draft hood.
(3) In special cases with high chimneys or flues,
the above schedule or areas may be modified sub-
ject to specific approval by the Bureau.
(4) In cases where the outlet from the equipment to
be converted is larger than the above indicated
size, an orifice plate may be inserted, or a
section of the flue pipe restricted to the size
indicated. The plate or restriction must be
installed between the equipment and'the draft
hood.
(5) The draft hood should ordinarily be located ad-
jacent to the equipment. In cases where it ap-
pears desirable to place the draft hood at a
distance from the equipment, the size of the
restricted section may be modified according to
the length and rise of the flue pipe.
(6) The proportioned section of the flue outlet of
the equipment eliminates the necessity of using
an adjustable damper in the flue pipe and such
damper will not be permitted.
(7) Where dampers are an integral part of the equip-
ment to be converted, tfiey shall be removed or
permanently secured in the wide open position,
except such dampers, the function of which is to
alter the passage of flue gases through appli-
ances, which shall be locked in such a position
as not to interfere with the normal operation of
the burners..
ME
. J
'a `l
c. Material used for flue pipe shall be such as to re-
sist the corrosive action of flue gases.
d. Flue pipe of existing systems shall be relocated
.� where necessary and new flue pipe installations shall be
made as to avoid sharp turns or other constructional
features which would create excessive resistance to the
flow of flue gases.
e. Changes in cross - sectional areas in flue pipe and
.venting systems shall be accomplished by properly design-
ed and tapered transformations or other similar appropriate
fittings and shall be subject to approval by the Bureau.
f. Flug pipe shall slope upward to the chimney at a
grade of not less than one quarter (%) inch per foot of length
unless otherwise approved by the Bureau.
g. Flue pipe shall be tightly connected to the chimney
liner so as to prevent infiltration ofJcold air.
h. No baffles shall be applied which will interfere
with the proper combustion of'the gas and /or proper vent-
ing of the equipment.
i. Flue pipe shall be well supported to prevent sagging
and shall not be installed closer than six (6) inches to
any combustible building materials unless flue pipe is cov-
ered with noncombustible insulation such that the surface
temperature of the exterior surface thereof will not exceed
one hundred twenty -five (125) degrees Fahrenheit when the
appliance is under full, continuous operation.
j. All space heating equipment shall be of the vented
type and properly vented to an effective flue. Space heaters
shall have one hundred (100) per cent shut -off.
k. Radiant heaters or other unvented heaters not exceed-
ing 25,000 BTU per hour input may be installed in fireplaces
providing therchimney has a positive draft with the damper
closed. "
Section 3 - that Section 16.05 Technical Regulations For
Gas Burner Installations, Exceeding 400,000 BTU Per Hour'Input
is hereby amended by adding the following to subsection 15 -
Air Intakes. - -
The area of fresh air intakes for combustion air and
equipment room ventilation shall be in accordance with
Section 16.07 Provisions For Combustion Air And Equipment
Room Ventilation For Gas Fired Equipment.
-5-
Section 4 - that Chapter 16 Gas Space Heating Requirements
is hereby amended by adding Section 16,07 Provisions For Com-
bustion Air find Equipment Room Ventilators For Gas;Fired Equip-
ment, which reads as follows:
16,07 Provisions For,Combustion Air And Equipment Room
Ventilators For Gas Fired Equipment
1.- For heating equipment °installed with a draft hood, the
air requirement for primary and secondary air,excess air, and
dilution air is 30 cubic feet for each cubic foot of gas input.
The following table for certain selected inputs-is based on a
reasonable velocity (300 FPMI) and a reasonable pressure drop
across the grilled intake (0.03 - 0.05" H20)
Overall
Input Air Reqd. Size of Intake (50% Free Area)
751000 BTUH
37.5 CFM
0..25•
sq. ft. or 36 -sq. In.
100;000 (
50
0,333
48
150, 000
75
0, 50-
72.
200,000
100
0,667.
96,
250,000
125.
0.,833 -
120
300,000
150
1.00-
144,
. 400, 000
200
1.333,
192. - -•
500,000
250
1.667
240:
600,000
_
300.
2.00.'
288
~ 700,000
350.
2.33
336
`800,000
400
2.667
384
r 9100,000
450.
3.00-
432.
• `I , 000, -000
500
3.33
480
2. For heating equipment installed with a barometric damp-
er, the excess air and dilution air requirements -are reduced
and total air requirement becomes 17.5 cubic feet for each
cubic foot of gas input, The following table is based on the
same velocity and pressure drop as in Section j .-
Input ,
Air Reqd.
400,000 BTUH
120 CFM
450,000
135
500,000
145
600,000
175
700,000
205
800,000
235
900,000
265
1,000,000
295
1,250,000
365
1,500,000
435
1,750,000
505
2,000,000
575
-6-
Overall
Size of Intake
(509 Free Area)
0.8 sq. ft.
115 sq. in.
0.9
130
0.97-
140
1.17
168
1..37-
197
1.57
226
1.77
255
1.97
284-
2.43
350
2.90
417.
3..37.
485,
3..83
552
a
r'
3. For heating equipment installed with uptake dampers or
other similar types of draft control equipment, the total air
requirement is 15 cubic feet of air for each cubic foot of
gas input. The following table is based on the same velocity
and pressure drop as in Sections 1, and 2..
Overall
Input Air Regd. Size of Intake (50% Free Area)
7501000 BTUH
187.5 CFM
1.25 sq. ft.
180 sq. in.
800,000
200.0
1.33
192
900,000
225.0
1.50
216
1,000,000
250.0
1.67
240
1,500,000
375.0
2.50
360
2,000,000
500.0
•3.33
480
2,500,000
625.0
4.17,
600
3,000,000
750..0
5.00
720
`f
It should be noted that the sizes indicated are for gravity
intakes communicating directly to the outdoors and, while al-
lowance has been made for ordinary equipment such as bird
screens, etc.., no allowance has been made for duct losses. Siz-
es shall be increased accordingly for any appreciable amount
of ductwork and /or other restrictions placed in the intake.
For systems equipped with an intake fan, the air requirements
indicated shall be used in determin' g fan caps it-ies.
For interio "r or alcove installations of e ui Ze t of ith6v-
nora a�]�.;�aental�;- siz'es:, with yentilatiori _aim j �t
,,,,�,w- ,_ from °inside.,, h�e
buiw��c�zng t ie `_�eFquireh!V of :National hoar
.x
_ a" Qfire .Under=
writens`-'Pam tvuo
p ,, g ,,w ones ate .top<.fehc]�o. sure and- one : pat'i bo„
tto; each
i��: "I'�wth; ':'free =` areaof�. oner(:�squ`ae- ,inch= M1pes�`•1000�'�BTtJH "nputy�
N. _ eri3 n x
411 —rd areas= haying
:ad''equate nfilftratiorZ fronf.7-th6`6:6t sid ver}titlation
Yme`thods - acceptable'.tinde,r requirements of- �NBM'54' sha�,l be- ,con -
°^ ;�� r
"- sdeyed' �.acceptab4le`by.:tYiisrBure,au "-where the above ,c'rYd`ij_ ons
do not a' `"''•N • n ` = 4' -
For.incinerato ,rs 1.5.CFM for each pound per hour capacity
shall be provided.,
Section 5 - that Section 18.17 Appliance Installation is
hereby amended by adding the following to item e,
The minimum area.for fresh air intakes for combustion air
and equipment room ventilation shall be in accordance with
Section 16.07 Provisions for Combustion Air And Equipment
Room Ventilation For Gas Fired Equipment;
Section 6 - that Section 19,03 Permit Regulations is hereby
amended by'deleting item a of subsection 1 Work For 'Which Permits
Are Required, which reads as follows,:
a. It shall hereafter be unlawful for any person, firm or
corporation to construct or install any heating plant or
equipment, such as is subject to regulation by the provisions
of this code, in or for any building or to alter or repair
-7-
any such existing heating plant or equipment, without first
making written application to and securing a permit from the
Bureau therefor, or to fail or neglect to comply with the
provisions of this code and of the permit so issued thereunder,
and any person, firm or corporation, when applying for any such
permit shall, upon-demand of said Bureau, furnish all necessary
plans, in duplicate, for such proposed construction, installa-
tion, alteration or repair and with all proper and sufficient
information relating thereto and shall secure the approval of
said plans before such permit shall be issued. All such plans-
and/or specifications, except for single family or two family
dwellings or for heating installations wherein the space to be
heated does not exceed 100,000 cubic feet, shall be prepared
and signed by a "Registered Professional�Engineer" duly qualified
by registration as required by "An Act to _Regulate the Practice
of Architecture,! Professional Engineering and Land Surveying,"
Chapter 523, Laws of 1921, as amended by Chapter 404, Laws of
1933,. State of Vinnesota,.and by no —other person or persons.
and substitute the I following in lieu thereof:
a. It shall be unlawful for any person, firm or corporation
to construct or install any heating plant or equipment in any
building or to alter or repair any existing heating plant or
equipment without first making written application to and secur-
ing a permit from the Bureau therefor, or to fail or neglect to
comply with the provisions of this code and of any permit is-
sued thereunder.{ Plans shall be required in duplicate as provid-
ed in Section 1.08 Permits (Application, Issuance and Regula-
tions). Plans shall include in addition to the details of the
system to be installed, the heat loss for each room or area in-
cluded in the space to be heated.
Section 7 - that Section 19.05 Regulations is hereby amended
by deleting paragraph c of subsection 9, which reads as follows:
c. On singlelboiler installations of low pressure steam
systems, the return connections shall preferably be made
through a water line loop connection without check valves
(Hartford connections). Whenever a gate valve is provided
on the steam outlet from any boiler, a gate valve shall be
placed in the corresponding return to the boiler.
and insert the following in lieu thereof:
c. On low pressure steam systems involving single or multi-
ple boilers with1gravit condensate return (including boiler re-
turn trap installations the return connections shall be made
through a Hartford connection and safety loop on each boiler.-
: The safety loop shall be of proper size as approved by the Bur-
: eau but not less than 2 -inch NPS, shall connect the steam out-
let or header tolthe return, and shall not be separated from
the boiler by any type of valve.
ray
Section 8' - that Section 19.05, Regulations, is hereby
amended by deleting paragraph e of Subsection 9, which reads
as follows: I
e. Each flow pressure steam boiler installation shall have
an equalizing pipe of proper size, not less then two (2) inch,
connecting the steam outlet or header, to the return.
and insert the following in lieu thereof:
e. Whenever a valve is provided on the steam outlet or
header of any boiler, a gate valve shall be placed in the
corresponding,return to the boiler. Whenever a low pressure
steam system incorporates a boiler feed, pumped return, or
combination feed - return device, at least one check valve and
one gate valve shall be installed, respectively, between the
device and the boiler with the gate valve being located as
close to the boiler as possible.
Section 9 ,, that Section 20.03 Warm Air Heating, Ventila-
tion And Sheet Metal Work Permit Regulations is'hereby amended
by deleting item, b of Subsection 2 Permit Application, Issu-
ance and Fees, which reads as follows:
b. No plan shall be approved or permit issued where the
building to be heated or ventilated exceeds 100,000 cubic
feet unless the plan so submitted shall be prepared and
signed by a registered professional engineer,duly qualified
by registration as required by an act to regulate the prac-
tice of architecture, professional engineering and land
t surveying, Chapter 523, Laws of Minnesota for 1921, as amend-
ed by Chapter 404, Laws of Minnesota for 1933, and Chapter
380, Laws of Minnesota for 1945. Provided, however, that
the Bureau may waive the above requirement of a permit in the
case of alterations or repairs to any existing warm air heat-
ing or ventilation systems where the cost of such altera-
tions or repairs will not add to the required capacity of
such heating or ventilating systems, and are not, in the opin-
ion of said Inspector, of such a nature as to render an in-
spection of the same necessary or desirable.
and insert the following in lieu thereof:
b. Plans shall be submitted in duplicate as provided in
Section 1.08 Permits (Application, Issuance and Regulations).
Section 10 - that Section 20.03 Warm Air Heating, Venti-
lation And Sheet Metal Work, Permit Regulations is hereby furth-
er amended by adding item c to subsection 3 Publications as
folio*.
c. The National Fire Protection Association Pamphlet 90A
(1963 Edition) Standards For The Installation of Air Condi-
tioning and Ventilation Systems of Other Than Residence Type
and Pamphlet 90B (1961 Edition) Standards For The Installa-
1st 2n
Laid over to
3rd and ap A dopte
Yeas Nays Yeas Nays
Dalglish Dalglish
Holland Holland
Loss Loss -7
Mortinson n Mortinson
Peterson (' / Peterson
-Remy- v Rosen
Mr. President V Mr. President Vavonlis
s
J PUBLIC =`�D ��