00-7a�����A�.
Presented
Referred To
Committee Date
1 BE IT RESOLVED, that the Council of the City of Saint Paul hereby certifies and approves the December 21,
2 1999, decision of the Legislative Hearing Officer on Properiy Code Enforcement Appeals far the following
3 addresses:
4 Propertv Aproealed
Appellant
6 1�04-1720-1740-1750 Norfolk Avenue Melvin Spiegler for Kleinman Rea1ty Co.
7 Decision; Variance granted on the nonconforming doors with the following conditions: 1) when the
S nonconforming doors need to be replaced, they will be replaced with confornung fire rated doors, 2) the
9 building must othercvise be in compliance.
10 1073 Thomas Avenue Anthony Bello
11 Decision: Variance granted with respect to the 1'/a" steel pipe in the floor on the laundry tubs and the kitchen
12 sink waste and vent as long as they function as intended. When they are not funcfioning correctly, they will
13 haue to be repaired.
14
15
16
17
18
19
20
Yeas Nays Absent
Blakey
Coleman �
Harris �
Benanav f
Reiter �
sostrom �
Lantry ✓
'� Q Ca
21 Adopted by Council: Date O
22 `
23 Adoption C ified by Council Se,c,retary
24 sy: '� � 1 � "
25 Approved by Mayor: Date �� �����
-�.
26 By:
Council File # �'da
Green Sheet # 101643
RESOLUTION
CITI( OF SAINT PAUL, MINNESOTA
1 � ;
Requested by Deparnnent of.
�
Form Approved by City Attorney
�
Approved by Mayor for Submission to Council
L•�
da'_ �
�.� W�,,,�
12-28-99
Gerry Straehman, 266-8560
January 5, 2000
wureaecae
ROUirt1G
OROFJt
TOTAL # OF SIGNATURE PAGES
GREEN SHEET
No 10164�3
u��� u��—
❑ a,,,.,.�. ❑ ��
❑ n'ewcc`uaEauicux ❑ nuwy�mmACCro
❑ WwRI���1M�1 ❑
(CLIP ALL LOCATIONS FOR SIGNATURE)
Approving the decision of the Legislative Hearing Officer on Property Code Enforcement
appeals for property at 17Q4-1720-1740-1750 Norfolk Avenue, and 1073 Thomas Avenue.
PLANNING COMMISSION
qBCOMMITTEE ,
CNVL SERV{CE CAMMISSION
liss thic oe�soNfi�m e.erwa�cea u�der a contrad rormis aevamneriCl
YES NO
Has thie peremRrcn ever been a eily emPbYeeT
YES NO
Does tAi� pe`son/fi'm poseess a sltill not �mallYP�d M' airy curtent ciry employee?
YES NQ '
Islhiape�sonfirmatargeledventloY? .
YES �
G;�e��;c�� ��s�ur�h G�n4ef
iw � � � � i�99
OFTR/WSACiION
COST7REVENUE BUDOETm IqRCLE ONE)
ACTMTY NUMBER
YEE HO
INFORMATON (IXPWf�
0 0 -'7
NOTES OF TI-� PROPERTY CODE ENFORCEMENT MEETING
Tuesday, December 21, 1999
Room 330 Courthouse
Czerry 5trathman, Legislative Hearing Officer
STAFF PRESENT: Bemie Arends, License, Inspection, Environmental Protection (LIEP); Tom
LeClair, LIEP; Don Wagner, LIEP
1704-1720-1740-1750 Norfolk Avenue
(Note: No one appeared representing the owner nor Fire Prevention; however, Mike Urmann,
Fire Prevention, said earlier that Fue Prevention has no objec6ons to the variance.)
Gerry Strathman granted a variance on the nonconforming doors with the following conditions:
1) when the nonconfornring doors need to be replaced, they wiil be replaced with conforming
fire rated doors, 2) the building must otherwise be in compliance.
1073 Thomas Avenue
Anthony and Patricia Bello, owners, appeared. Mr. Bello stated this is about an order dated 7-2-
98. He is appealing two items on that order. The first is Plumbing Item #1, 1'h" steel pipe into
floar on laundry tubs; install waste and vent as per code. Mr. Bello's justification for an appeal
is as follows: The waste line is an exisring 1%2" galvanized pipe. The pipe is in good condition,
no evidence of deteriorarion and does not warrant replacement. To replace this pipe
(approxnnately 1 to 2 feet) would require breaking the concrete floor to make new connection to
the sewer line. This is not necessary because the pipe is existing, in good condi6on, and should
be left in-place. The pipe is just a material, whether galvanized or PVC.
Tom Leclair reported neither 1'/z" steel pipe nor galvanized steel pipe have ever been allowed
under the floor. That was put in without a permit yeazs back and has never been approved. LIEP
is asking it to be replaced.
Gerry Strathman asked when this was done. Mr. Bello responded the house was built in 1921.
This pipe may be original construction. Mr. LeClair responded this was not done under code in
1921 either because it was not until the 1940's after the war years when houses had laundry trays.
The 1'/i' was probably put in without a permit.
What is the functional problem with 1%z' galvanized pipe, asked Mr. StraYhman. Mr. LeCiair
responded it does not produce the protecfive oxidation as cast iron. The thread areas eventually
rot out and there is sewage going into the soil instead of down to the pipe. Also, anythiug under
ground has to be at least two inches.
Mr. Strathman asked does he need to take up the concrete floor in order to comply. Mr. LeClair
responded it depends on how far the 1'/z' pipe goes down. There may be a vertical piece going
into it. Bernie Arends stated a person cannot see what is there until the floor is taken up.
00 -?
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 2
The pipe above the floor, stated Mr. Bello, is in good condition. When the house was built, it
served the purpose of what it was suppose to do then and it is still doing the same thing now.
Mr. LeClair responded the plumbing code in Saint Paul goes back to 1889.
Mr. Strathman asked about the second issue. Mr. Bello responded that is Plumbing Item #4,
install kitchen sink waste and vent as per code. His justification for an appeal is as follows: The
vent and waste line under the kitchen sink are existing and appeazs to be in good condition. The
waste line has been replaced but not the vent pipe. For the vent pipe to comply with e�sting
code would require its relocation, which would also require the removal of kitchen sink and
cabinet and the breaking of old plaster walls to gain access to the e�sting vent in order to make
all necessary connections to meet current code. The existing vent is in good condition, the
amount of work needed to bring it to code is enormous and should be grandfathered in.
Mr. Arends stated part of the waste pipe has been replaced as PVC. It was done incorrectly
because it caused the galvanized piping in the basement to pitch backwards. They used what is
called a rubber 90 with a couple of clamps, which is not code today. Per code, if work is done on
a fixture, it should be brought up to the current code. The vent is not up to code because it runs
below the spili line of the fixture and the wall and considered a flat vent. It has to run vertically
until it gets above the spill line of the fixture. This is why it is being asked to be changed.
Mr. Strathman asked for the implication of it. Mr. Arends responded if the waste line plugs up,
water can back into that vent. It would leave behind whatever was in it: dirt, grease, etc.
This vent does not carry water, stated Mr. Bello. It is to vent the gas out.
Mr. LeClair responded the vent on the kitchen sink is to maintain water pressure so that it does
not siphon the trap seal. If the trap seal is siphoned, then there is a chance of getting organisms
through the trap seal into the building. There is no longer a sanitary and storm sewer
combination, but straight storm and straight sanitary so there is no delusion in the sewer systems.
The pipe that goes through the roof vents the sewer systems. The problem is there is higher
concentrations of hydrogen sulfide gas in the building than ever before because there is no
delusion from the combination sewer, storm, and sanitary. If the trap is lost, there is a possibility
if the conditions are right, that bad materials could enter the house. That is why there is always a
vent in every fixture trap to maintain the seaL If there is not a vent, there is a chance of losing
the trap seal.
Mr. Bello stated the plumber that was there and the inspector said the only thing that needs to be
done is to make it a 45 degree connection. Mr. LeClair responded 45 degrees or to vertical is
what the code says. Until it gets above the spill line above the fixture, added Mr. Arends.
He disagrees that bacteria will form in it, stated Mr. Bello. There is a sewer line that goes down
into a trap in the basement to the sewer connection. This is to prevent any gas from building up
in the unit. Therefore, the vent is there to pipe it out through the roof.
QFj
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 3
He does not doubt the City stafF aze correct, stated Mr. Strathman. The question is aze the
potential hazards sufficient to require the homeowner to make the changes necessary to bring it
into compliance. Mr. Strathman asked is there an estimate for the repairs. Mr. Bello responded
no because the plumber does not know what he will find. The vent is there, but in order to make
the connection, the plumber may have to relocate it or break down the wa11 in order to find it.
Mr. Strathman asked about the other items on the list. Mr. Bello responded the rest of the items
have been taken caze of.
Patricia Beilo asked is there a way to make sure that the vent is operational. Mr. LeClair
responded until it is established where the vent is in the wall, there is no way to check it. Don
Wagner responded one way is to fill up the compartment with water, let the water run, and listen
for a gurgling sound at the end.
Mr. LeClair stated another issue is the water heater, which was installed without a permit. Mr.
Bello responded he was told by the inspector that the plumber can get the pernut for it. Mr.
Wagner responded the only thing in quesrions are the 2 items Mr. Bello is appealing. Mr.
Wagner's understanding is there would be a permit taken out for the water heater.
Mr. Strathman granted the variance with respect to the 1'/a" steel pipe in the floor on the laundry
tubs and the kitchen sink waste and vent as long as they function as intended. The other repairs
haue been done, and neither of these items in questions are an imminent health hazazd, though
there may be a long term health h�rd. City staff is correct in citing this, and Mr. Strathman
accepts their determination that this is a violarion of code. The correction on both of them would
be a financial burden that is not warranted. When these items aze not functioning conectly, they
will haue to be repaired.
The meeting was adjourned at 1:50 p.m.
�
a�����A�.
Presented
Referred To
Committee Date
1 BE IT RESOLVED, that the Council of the City of Saint Paul hereby certifies and approves the December 21,
2 1999, decision of the Legislative Hearing Officer on Properiy Code Enforcement Appeals far the following
3 addresses:
4 Propertv Aproealed
Appellant
6 1�04-1720-1740-1750 Norfolk Avenue Melvin Spiegler for Kleinman Rea1ty Co.
7 Decision; Variance granted on the nonconforming doors with the following conditions: 1) when the
S nonconforming doors need to be replaced, they will be replaced with confornung fire rated doors, 2) the
9 building must othercvise be in compliance.
10 1073 Thomas Avenue Anthony Bello
11 Decision: Variance granted with respect to the 1'/a" steel pipe in the floor on the laundry tubs and the kitchen
12 sink waste and vent as long as they function as intended. When they are not funcfioning correctly, they will
13 haue to be repaired.
14
15
16
17
18
19
20
Yeas Nays Absent
Blakey
Coleman �
Harris �
Benanav f
Reiter �
sostrom �
Lantry ✓
'� Q Ca
21 Adopted by Council: Date O
22 `
23 Adoption C ified by Council Se,c,retary
24 sy: '� � 1 � "
25 Approved by Mayor: Date �� �����
-�.
26 By:
Council File # �'da
Green Sheet # 101643
RESOLUTION
CITI( OF SAINT PAUL, MINNESOTA
1 � ;
Requested by Deparnnent of.
�
Form Approved by City Attorney
�
Approved by Mayor for Submission to Council
L•�
da'_ �
�.� W�,,,�
12-28-99
Gerry Straehman, 266-8560
January 5, 2000
wureaecae
ROUirt1G
OROFJt
TOTAL # OF SIGNATURE PAGES
GREEN SHEET
No 10164�3
u��� u��—
❑ a,,,.,.�. ❑ ��
❑ n'ewcc`uaEauicux ❑ nuwy�mmACCro
❑ WwRI���1M�1 ❑
(CLIP ALL LOCATIONS FOR SIGNATURE)
Approving the decision of the Legislative Hearing Officer on Property Code Enforcement
appeals for property at 17Q4-1720-1740-1750 Norfolk Avenue, and 1073 Thomas Avenue.
PLANNING COMMISSION
qBCOMMITTEE ,
CNVL SERV{CE CAMMISSION
liss thic oe�soNfi�m e.erwa�cea u�der a contrad rormis aevamneriCl
YES NO
Has thie peremRrcn ever been a eily emPbYeeT
YES NO
Does tAi� pe`son/fi'm poseess a sltill not �mallYP�d M' airy curtent ciry employee?
YES NQ '
Islhiape�sonfirmatargeledventloY? .
YES �
G;�e��;c�� ��s�ur�h G�n4ef
iw � � � � i�99
OFTR/WSACiION
COST7REVENUE BUDOETm IqRCLE ONE)
ACTMTY NUMBER
YEE HO
INFORMATON (IXPWf�
0 0 -'7
NOTES OF TI-� PROPERTY CODE ENFORCEMENT MEETING
Tuesday, December 21, 1999
Room 330 Courthouse
Czerry 5trathman, Legislative Hearing Officer
STAFF PRESENT: Bemie Arends, License, Inspection, Environmental Protection (LIEP); Tom
LeClair, LIEP; Don Wagner, LIEP
1704-1720-1740-1750 Norfolk Avenue
(Note: No one appeared representing the owner nor Fire Prevention; however, Mike Urmann,
Fire Prevention, said earlier that Fue Prevention has no objec6ons to the variance.)
Gerry Strathman granted a variance on the nonconforming doors with the following conditions:
1) when the nonconfornring doors need to be replaced, they wiil be replaced with conforming
fire rated doors, 2) the building must otherwise be in compliance.
1073 Thomas Avenue
Anthony and Patricia Bello, owners, appeared. Mr. Bello stated this is about an order dated 7-2-
98. He is appealing two items on that order. The first is Plumbing Item #1, 1'h" steel pipe into
floar on laundry tubs; install waste and vent as per code. Mr. Bello's justification for an appeal
is as follows: The waste line is an exisring 1%2" galvanized pipe. The pipe is in good condition,
no evidence of deteriorarion and does not warrant replacement. To replace this pipe
(approxnnately 1 to 2 feet) would require breaking the concrete floor to make new connection to
the sewer line. This is not necessary because the pipe is existing, in good condi6on, and should
be left in-place. The pipe is just a material, whether galvanized or PVC.
Tom Leclair reported neither 1'/z" steel pipe nor galvanized steel pipe have ever been allowed
under the floor. That was put in without a permit yeazs back and has never been approved. LIEP
is asking it to be replaced.
Gerry Strathman asked when this was done. Mr. Bello responded the house was built in 1921.
This pipe may be original construction. Mr. LeClair responded this was not done under code in
1921 either because it was not until the 1940's after the war years when houses had laundry trays.
The 1'/i' was probably put in without a permit.
What is the functional problem with 1%z' galvanized pipe, asked Mr. StraYhman. Mr. LeCiair
responded it does not produce the protecfive oxidation as cast iron. The thread areas eventually
rot out and there is sewage going into the soil instead of down to the pipe. Also, anythiug under
ground has to be at least two inches.
Mr. Strathman asked does he need to take up the concrete floor in order to comply. Mr. LeClair
responded it depends on how far the 1'/z' pipe goes down. There may be a vertical piece going
into it. Bernie Arends stated a person cannot see what is there until the floor is taken up.
00 -?
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 2
The pipe above the floor, stated Mr. Bello, is in good condition. When the house was built, it
served the purpose of what it was suppose to do then and it is still doing the same thing now.
Mr. LeClair responded the plumbing code in Saint Paul goes back to 1889.
Mr. Strathman asked about the second issue. Mr. Bello responded that is Plumbing Item #4,
install kitchen sink waste and vent as per code. His justification for an appeal is as follows: The
vent and waste line under the kitchen sink are existing and appeazs to be in good condition. The
waste line has been replaced but not the vent pipe. For the vent pipe to comply with e�sting
code would require its relocation, which would also require the removal of kitchen sink and
cabinet and the breaking of old plaster walls to gain access to the e�sting vent in order to make
all necessary connections to meet current code. The existing vent is in good condition, the
amount of work needed to bring it to code is enormous and should be grandfathered in.
Mr. Arends stated part of the waste pipe has been replaced as PVC. It was done incorrectly
because it caused the galvanized piping in the basement to pitch backwards. They used what is
called a rubber 90 with a couple of clamps, which is not code today. Per code, if work is done on
a fixture, it should be brought up to the current code. The vent is not up to code because it runs
below the spili line of the fixture and the wall and considered a flat vent. It has to run vertically
until it gets above the spill line of the fixture. This is why it is being asked to be changed.
Mr. Strathman asked for the implication of it. Mr. Arends responded if the waste line plugs up,
water can back into that vent. It would leave behind whatever was in it: dirt, grease, etc.
This vent does not carry water, stated Mr. Bello. It is to vent the gas out.
Mr. LeClair responded the vent on the kitchen sink is to maintain water pressure so that it does
not siphon the trap seal. If the trap seal is siphoned, then there is a chance of getting organisms
through the trap seal into the building. There is no longer a sanitary and storm sewer
combination, but straight storm and straight sanitary so there is no delusion in the sewer systems.
The pipe that goes through the roof vents the sewer systems. The problem is there is higher
concentrations of hydrogen sulfide gas in the building than ever before because there is no
delusion from the combination sewer, storm, and sanitary. If the trap is lost, there is a possibility
if the conditions are right, that bad materials could enter the house. That is why there is always a
vent in every fixture trap to maintain the seaL If there is not a vent, there is a chance of losing
the trap seal.
Mr. Bello stated the plumber that was there and the inspector said the only thing that needs to be
done is to make it a 45 degree connection. Mr. LeClair responded 45 degrees or to vertical is
what the code says. Until it gets above the spill line above the fixture, added Mr. Arends.
He disagrees that bacteria will form in it, stated Mr. Bello. There is a sewer line that goes down
into a trap in the basement to the sewer connection. This is to prevent any gas from building up
in the unit. Therefore, the vent is there to pipe it out through the roof.
QFj
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 3
He does not doubt the City stafF aze correct, stated Mr. Strathman. The question is aze the
potential hazards sufficient to require the homeowner to make the changes necessary to bring it
into compliance. Mr. Strathman asked is there an estimate for the repairs. Mr. Bello responded
no because the plumber does not know what he will find. The vent is there, but in order to make
the connection, the plumber may have to relocate it or break down the wa11 in order to find it.
Mr. Strathman asked about the other items on the list. Mr. Bello responded the rest of the items
have been taken caze of.
Patricia Beilo asked is there a way to make sure that the vent is operational. Mr. LeClair
responded until it is established where the vent is in the wall, there is no way to check it. Don
Wagner responded one way is to fill up the compartment with water, let the water run, and listen
for a gurgling sound at the end.
Mr. LeClair stated another issue is the water heater, which was installed without a permit. Mr.
Bello responded he was told by the inspector that the plumber can get the pernut for it. Mr.
Wagner responded the only thing in quesrions are the 2 items Mr. Bello is appealing. Mr.
Wagner's understanding is there would be a permit taken out for the water heater.
Mr. Strathman granted the variance with respect to the 1'/a" steel pipe in the floor on the laundry
tubs and the kitchen sink waste and vent as long as they function as intended. The other repairs
haue been done, and neither of these items in questions are an imminent health hazazd, though
there may be a long term health h�rd. City staff is correct in citing this, and Mr. Strathman
accepts their determination that this is a violarion of code. The correction on both of them would
be a financial burden that is not warranted. When these items aze not functioning conectly, they
will haue to be repaired.
The meeting was adjourned at 1:50 p.m.
�
a�����A�.
Presented
Referred To
Committee Date
1 BE IT RESOLVED, that the Council of the City of Saint Paul hereby certifies and approves the December 21,
2 1999, decision of the Legislative Hearing Officer on Properiy Code Enforcement Appeals far the following
3 addresses:
4 Propertv Aproealed
Appellant
6 1�04-1720-1740-1750 Norfolk Avenue Melvin Spiegler for Kleinman Rea1ty Co.
7 Decision; Variance granted on the nonconforming doors with the following conditions: 1) when the
S nonconforming doors need to be replaced, they will be replaced with confornung fire rated doors, 2) the
9 building must othercvise be in compliance.
10 1073 Thomas Avenue Anthony Bello
11 Decision: Variance granted with respect to the 1'/a" steel pipe in the floor on the laundry tubs and the kitchen
12 sink waste and vent as long as they function as intended. When they are not funcfioning correctly, they will
13 haue to be repaired.
14
15
16
17
18
19
20
Yeas Nays Absent
Blakey
Coleman �
Harris �
Benanav f
Reiter �
sostrom �
Lantry ✓
'� Q Ca
21 Adopted by Council: Date O
22 `
23 Adoption C ified by Council Se,c,retary
24 sy: '� � 1 � "
25 Approved by Mayor: Date �� �����
-�.
26 By:
Council File # �'da
Green Sheet # 101643
RESOLUTION
CITI( OF SAINT PAUL, MINNESOTA
1 � ;
Requested by Deparnnent of.
�
Form Approved by City Attorney
�
Approved by Mayor for Submission to Council
L•�
da'_ �
�.� W�,,,�
12-28-99
Gerry Straehman, 266-8560
January 5, 2000
wureaecae
ROUirt1G
OROFJt
TOTAL # OF SIGNATURE PAGES
GREEN SHEET
No 10164�3
u��� u��—
❑ a,,,.,.�. ❑ ��
❑ n'ewcc`uaEauicux ❑ nuwy�mmACCro
❑ WwRI���1M�1 ❑
(CLIP ALL LOCATIONS FOR SIGNATURE)
Approving the decision of the Legislative Hearing Officer on Property Code Enforcement
appeals for property at 17Q4-1720-1740-1750 Norfolk Avenue, and 1073 Thomas Avenue.
PLANNING COMMISSION
qBCOMMITTEE ,
CNVL SERV{CE CAMMISSION
liss thic oe�soNfi�m e.erwa�cea u�der a contrad rormis aevamneriCl
YES NO
Has thie peremRrcn ever been a eily emPbYeeT
YES NO
Does tAi� pe`son/fi'm poseess a sltill not �mallYP�d M' airy curtent ciry employee?
YES NQ '
Islhiape�sonfirmatargeledventloY? .
YES �
G;�e��;c�� ��s�ur�h G�n4ef
iw � � � � i�99
OFTR/WSACiION
COST7REVENUE BUDOETm IqRCLE ONE)
ACTMTY NUMBER
YEE HO
INFORMATON (IXPWf�
0 0 -'7
NOTES OF TI-� PROPERTY CODE ENFORCEMENT MEETING
Tuesday, December 21, 1999
Room 330 Courthouse
Czerry 5trathman, Legislative Hearing Officer
STAFF PRESENT: Bemie Arends, License, Inspection, Environmental Protection (LIEP); Tom
LeClair, LIEP; Don Wagner, LIEP
1704-1720-1740-1750 Norfolk Avenue
(Note: No one appeared representing the owner nor Fire Prevention; however, Mike Urmann,
Fire Prevention, said earlier that Fue Prevention has no objec6ons to the variance.)
Gerry Strathman granted a variance on the nonconforming doors with the following conditions:
1) when the nonconfornring doors need to be replaced, they wiil be replaced with conforming
fire rated doors, 2) the building must otherwise be in compliance.
1073 Thomas Avenue
Anthony and Patricia Bello, owners, appeared. Mr. Bello stated this is about an order dated 7-2-
98. He is appealing two items on that order. The first is Plumbing Item #1, 1'h" steel pipe into
floar on laundry tubs; install waste and vent as per code. Mr. Bello's justification for an appeal
is as follows: The waste line is an exisring 1%2" galvanized pipe. The pipe is in good condition,
no evidence of deteriorarion and does not warrant replacement. To replace this pipe
(approxnnately 1 to 2 feet) would require breaking the concrete floor to make new connection to
the sewer line. This is not necessary because the pipe is existing, in good condi6on, and should
be left in-place. The pipe is just a material, whether galvanized or PVC.
Tom Leclair reported neither 1'/z" steel pipe nor galvanized steel pipe have ever been allowed
under the floor. That was put in without a permit yeazs back and has never been approved. LIEP
is asking it to be replaced.
Gerry Strathman asked when this was done. Mr. Bello responded the house was built in 1921.
This pipe may be original construction. Mr. LeClair responded this was not done under code in
1921 either because it was not until the 1940's after the war years when houses had laundry trays.
The 1'/i' was probably put in without a permit.
What is the functional problem with 1%z' galvanized pipe, asked Mr. StraYhman. Mr. LeCiair
responded it does not produce the protecfive oxidation as cast iron. The thread areas eventually
rot out and there is sewage going into the soil instead of down to the pipe. Also, anythiug under
ground has to be at least two inches.
Mr. Strathman asked does he need to take up the concrete floor in order to comply. Mr. LeClair
responded it depends on how far the 1'/z' pipe goes down. There may be a vertical piece going
into it. Bernie Arends stated a person cannot see what is there until the floor is taken up.
00 -?
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 2
The pipe above the floor, stated Mr. Bello, is in good condition. When the house was built, it
served the purpose of what it was suppose to do then and it is still doing the same thing now.
Mr. LeClair responded the plumbing code in Saint Paul goes back to 1889.
Mr. Strathman asked about the second issue. Mr. Bello responded that is Plumbing Item #4,
install kitchen sink waste and vent as per code. His justification for an appeal is as follows: The
vent and waste line under the kitchen sink are existing and appeazs to be in good condition. The
waste line has been replaced but not the vent pipe. For the vent pipe to comply with e�sting
code would require its relocation, which would also require the removal of kitchen sink and
cabinet and the breaking of old plaster walls to gain access to the e�sting vent in order to make
all necessary connections to meet current code. The existing vent is in good condition, the
amount of work needed to bring it to code is enormous and should be grandfathered in.
Mr. Arends stated part of the waste pipe has been replaced as PVC. It was done incorrectly
because it caused the galvanized piping in the basement to pitch backwards. They used what is
called a rubber 90 with a couple of clamps, which is not code today. Per code, if work is done on
a fixture, it should be brought up to the current code. The vent is not up to code because it runs
below the spili line of the fixture and the wall and considered a flat vent. It has to run vertically
until it gets above the spill line of the fixture. This is why it is being asked to be changed.
Mr. Strathman asked for the implication of it. Mr. Arends responded if the waste line plugs up,
water can back into that vent. It would leave behind whatever was in it: dirt, grease, etc.
This vent does not carry water, stated Mr. Bello. It is to vent the gas out.
Mr. LeClair responded the vent on the kitchen sink is to maintain water pressure so that it does
not siphon the trap seal. If the trap seal is siphoned, then there is a chance of getting organisms
through the trap seal into the building. There is no longer a sanitary and storm sewer
combination, but straight storm and straight sanitary so there is no delusion in the sewer systems.
The pipe that goes through the roof vents the sewer systems. The problem is there is higher
concentrations of hydrogen sulfide gas in the building than ever before because there is no
delusion from the combination sewer, storm, and sanitary. If the trap is lost, there is a possibility
if the conditions are right, that bad materials could enter the house. That is why there is always a
vent in every fixture trap to maintain the seaL If there is not a vent, there is a chance of losing
the trap seal.
Mr. Bello stated the plumber that was there and the inspector said the only thing that needs to be
done is to make it a 45 degree connection. Mr. LeClair responded 45 degrees or to vertical is
what the code says. Until it gets above the spill line above the fixture, added Mr. Arends.
He disagrees that bacteria will form in it, stated Mr. Bello. There is a sewer line that goes down
into a trap in the basement to the sewer connection. This is to prevent any gas from building up
in the unit. Therefore, the vent is there to pipe it out through the roof.
QFj
PROPERTY CODE ENFORCEMENT OF 12-21-99
Page 3
He does not doubt the City stafF aze correct, stated Mr. Strathman. The question is aze the
potential hazards sufficient to require the homeowner to make the changes necessary to bring it
into compliance. Mr. Strathman asked is there an estimate for the repairs. Mr. Bello responded
no because the plumber does not know what he will find. The vent is there, but in order to make
the connection, the plumber may have to relocate it or break down the wa11 in order to find it.
Mr. Strathman asked about the other items on the list. Mr. Bello responded the rest of the items
have been taken caze of.
Patricia Beilo asked is there a way to make sure that the vent is operational. Mr. LeClair
responded until it is established where the vent is in the wall, there is no way to check it. Don
Wagner responded one way is to fill up the compartment with water, let the water run, and listen
for a gurgling sound at the end.
Mr. LeClair stated another issue is the water heater, which was installed without a permit. Mr.
Bello responded he was told by the inspector that the plumber can get the pernut for it. Mr.
Wagner responded the only thing in quesrions are the 2 items Mr. Bello is appealing. Mr.
Wagner's understanding is there would be a permit taken out for the water heater.
Mr. Strathman granted the variance with respect to the 1'/a" steel pipe in the floor on the laundry
tubs and the kitchen sink waste and vent as long as they function as intended. The other repairs
haue been done, and neither of these items in questions are an imminent health hazazd, though
there may be a long term health h�rd. City staff is correct in citing this, and Mr. Strathman
accepts their determination that this is a violarion of code. The correction on both of them would
be a financial burden that is not warranted. When these items aze not functioning conectly, they
will haue to be repaired.
The meeting was adjourned at 1:50 p.m.
�